Analysis for 3P4W, 3P3W, 1P2W, 1P3W
True RMS Value(V 123 and L 123 )
Active Power(W, KW, MW, GW)
Apparent and Reactive Power (KVA, KVAR)
Power Factor (PF), Phase Angle (Φ)
Energy (WH, KWH, KVARH, PFH)
Current Measurement from 0.1mA to 3000A, Capable of Analyzing IT Standby Power Consumption to the Maximum Demand of a Factory
Display of 35 Parameters in One Screen(3P4W)
rogrammable CT (1 to 600) and PT (1 to 3000) Ratios
Display of Overlapped Voltage and Current Waveform
2.4M Memory with Programmable Interval (1 to 6000 seconds, 17000 Records for 3P4W System)
Output of Waveform, Power Parameters and Harmonics at Command
Large Dot Matrix LCD Display with Backlight
Average Demand (AD in W, KW, MW)
aximum Demand (MD in W, KW, MW) with Programmable Period
Harmonic Analysis to the 99th Order
Display of 50 Harmonics in One Screen with Waveform
Display of Waveform with Peak Values (1024 Samples/Period)
Analysis of Total Harmonic Distortion (%THD-F)
Graphic Phasor Diagram with 3 Phase System Parameters
Capture 28 Transient Events (Time+Cycles) with Programmable Threshold(%)
3 Phase Voltage Unbalance Ratio (VUR)
3 Phase Voltage Unbalance Factor (d0%, d2%)
Calculated Unbalance Current through Neutral Line (In)
Optical isolated USB Interface
Built-in Timer and Calendar for Data Logging
onductor Size: -Model 6801 30mm(approx) -Model 6802 5
55mm(approx),64*24mm(bus bar) -Model 3007 170mm(approx)
* Please refer to users manual for more detailed and up-to-date description of specification
AC Watt (50 or 60 Hz, PF 0.5 to 1, CT=1)
Range Resolution Accuracy of Readings
6800+6801
6800+6802
6800+3007
5.0 – 999.9W 0.1W ±1% ± 8dgts ±1% ± 8dgts ±1% of VA Range ±8dgts
1.000 – 9.999 KW 0.001 KW ±1% ± 8 dgts ±1% ± 8 dgts ±1% of VA Range ±8dgts
10.00 – 99.99 KW 0.01 KW ±1% ± 8 dgts ±1% ± 8 dgts ±1% of VA Range ±8dgts
100.0 – 999.9 KW 0.1 KW ±1% ± 8dgts ±1% ± 8dgts ±1% of VA Range ±8dgts
1000 – 9999 KW 1 KW ±1% ± 8dgts ±1% ± 8dgts ±1% of VA Range ±8dgts
0.000 – 9.999MW 0.001MW
– ±1% ± 8 dgts ±1% of VA Range ±8dgts
AC Current( 50 or 60Hz, Auto Range,True RMS,Crest Factor<4,CT=1)
Range Resolution Accuracy of Readings
6800+6801
(Overload Protection AC200A)
0.050 – 9.999A 0.001A ±0.5% ± 5dgts
10.00 – 60.00A 0.01A ±0.5% ± 5dgts
60.00 – 99.99A 0.01A ±1.0% ± 5dgts
6800+6802
(Overload Protection AC2000A)
0.04 – 10.00A 0.01A –
0.4A – 100.0A 0.1A ±0.5% ± 5dgts
4.0 – 1000.0A 1A ±0.5% ± 5dgts
6800+ 3007
(Overload Protection AC3500A)
4 – 300A 0.1A ±1% of Range ±5dgts
300.0 – 999.9A 0.1A ±1% of Range ±5dgts
1000 – 3000A 1A ±1% of Range ±5dgts
AC Voltage (50 or 60 Hz, Auto Range, True RMS, Crest FActor<4)
Range Resolution Accuracy of Readings Range Resolution Accuracy of Readings
4.0V – 500.0 (Phase to Neutral)
0.1V
± 0.5% ± 5dgts
4.0V –600.0V (Phase to phase)